Debugging Complete Integrated Test Bench Product Features:
1. Can accurately measure the capacity of various transformers, convenient and accurate;
2. Can measure no-load current, no-load loss, short-circuit voltage, short-circuit loss, and zero-sequence impedance of various types of transformers;
3. Can automatically perform waveform distortion correction, temperature correction, voltage correction, and current correction. The operator only needs to input the correction index according to the transformer type, and the instrument can automatically calculate the corrected result. It is very suitable for units that do not have conditions for short-circuit tests on slightly larger capacity transformers;
4. Allows external connection of voltage transformers and current transformers for extended range measurement, and can measure test objects with any parameters;
5. Wide voltage range: maximum measurable voltage up to 750V, accuracy guaranteed without switching gears. No damage to the instrument due to incorrect voltage gear selection;
6. Large screen, high-brightness LCD display, full Chinese menu and operation prompts for friendly human-machine dialogue, buttons for easier operation, wide-temperature LCD with brightness adjustment, adaptable to all seasons;
7. Users can print out test data at any time through the micro printer.
Debugging Complete Integrated Test Bench Main Performance
Adopts three-phase four-wire input mode, AC380V input;
Three-phase voltage AC380V fixed voltage output one group (current less than or equal to 10A)
Three-phase voltage AC0-430V adjustable output one group (current less than or equal to 10A)
Three-phase current AC0-10A adjustable output one group (voltage less than or equal to 10V)
Three-phase current AC0-10A adjustable output one group, independent voltage regulation output, with capacitor switching in/out; reactor switching in/out functions (for verifying reactive power compensation characteristics of capacitor cabinets)
Phase sequence detection function: 0-480V voltage, can determine positive phase sequence, negative phase sequence;
Electric stopwatch timing function: starts timing after collecting the capacitor cabinet switch signal, stops timing when the switch signal disappears;
All display instruments use national standard universal 44L1 pointer meters, convenient for inspection and replacement, accuracy class 1.5;
Equipped with 3-inch universal wheels for easy movement;
DC fixed voltages 12V, 24V, 36V, 110V, 220V, current less than or equal to 20A.
Input circuit is equipped with air switch, output circuit is equipped with fuse, overcurrent will not damage the instrument.
Technical Parameters:
Input Power: Three-phase four-wire AC380V
Output Voltage and Current:
1. Three-phase AC 0 – 10A output (<100V, adjustable value> one group
2. Three-phase AC100V output (fixed value) one group
3. AC operation voltage output AC 0~400V, at 220V, current less than 10A
4. DC operation voltage output DC 0~260V
5 Single-phase AC220V output (fixed value, socket form) two groups,
6 Three-phase AC380V output (fixed value, terminal form) one group,
Usage Instructions:
1. Connect three-phase four-wire AC380V
2. Connect output DC300V to the load
3. Rotate the output adjustment knob counterclockwise to zero.
4. Check and confirm the wiring is correct
5. Close the power switch
6. Slowly adjust the output adjustment knob to raise the voltage to a suitable value.
7. After the test, first rotate the output adjustment knob counterclockwise to zero, then turn off the power switch. After discharge is complete, you can start disconnecting the wires.