Technical Parameters:
The 1000V digital ground resistance tester adopts the current-voltage method testing principle, also known as the four-wire method testing technology. The current source supplies current to the measured resistance Rx through the "I+, I-" two ports (also called I-type ports). The current magnitude is read by the ammeter I. The voltage drop across Rx is taken from the "V+, V-" two ports (also called V-type ports) and read by the voltmeter V. By measuring I and V, the resistance value of the measured resistor can be calculated.
1000V Digital Ground Resistance Tester / Electric Power Installation, Repair and Test Qualification
1. Measurement range: 0~2999.9μΩ
2. Resolution: 0~99.99, 0.01μΩ; 100.0~2999.9, 0.1μΩ
3. Test current: DC50A, 100A, 150A, 200A four fixed output levels
4. Measurement accuracy: ±(0.5% rd+2d)
5. Continuous working time: 5s~599s
6. Display: large-screen Chinese LCD display
7. Communication: USB or RS232 serial port
8. Power supply: AC220V±10% 50Hz
9. Total power: 1200W
10. Maximum stored records: 200
11. Working environment: temperature -10℃~40℃ humidity ≤80 %RH
12. Volume: 380×300×260 mm3
13. Weight: 8kg (excluding accessories)