Exploring the Standard Parameters and Pre-Use Preparation of DC High Voltage Generator
DC high voltage generator is designed for maintenance-free operation, with main components using imported technology components, durable and resistant to continuous direct short-circuit discharge to ground. The DC high voltage generator has high precision and accurate measurement. Both voltage and current meters are digital displays, with voltage resolution of 0.1kV and current resolution of 0.1uA. The voltage meter on the control box directly displays the voltage value applied to the load test object, so no external voltage divider is needed, and wiring is simple. The instrument has the ability to measure leakage current at both high and low voltage ends. The high voltage end uses a circular shielded digital meter display, which is resistant to discharge impact and has good anti-interference performance, suitable for on-site use.
The voltage regulation stability of the DC high voltage generator is high, with smooth voltage regulation across the full range. The output voltage adjustment uses a single imported multi-turn potentiometer, ensuring a stable boosting process and high adjustment precision, and is designed with coarse and fine adjustment functions. The voltage adjustment accuracy is better than 0.1%, the voltage and current measurement error is less than 1.0%, and the ripple factor is better than 0.5%.
Do not ignore the pre-use preparation of the DC high voltage generator:
1. Before using the DC high voltage generator, check its integrity. The connecting cables should not have open circuits or short circuits, and the equipment should have no damage such as cracks.
2. Take the voltage doubling cylinder out of the chassis and place it in a suitable safe position. Connect the power cord, cable, and grounding wire respectively. The protective grounding wire, working grounding wire, and the grounding wire of the discharge rod should all be separately connected to the ground wire of the test object. It is strictly forbidden to connect the grounding wires in series with each other. Therefore, a dedicated grounding wire should be used.
4. To ensure personal safety, we repeatedly remind users to pay attention to the proper grounding of the control box and the voltage doubling cylinder, as well as the discharge of the test object and the voltage doubling cylinder after shutdown.
5. Prevent foreign objects from entering the control box. If the control box has a fan, check regularly whether the fan is operating normally.
6. When the insulating cylinder of the voltage doubling cylinder is dirty, wipe it clean with a dry cloth. Do not use organic solvents such as alcohol or gasoline. It can be cleaned with detergent on the surface of the insulating cylinder, and can only be used after air drying. When transporting or not in use, put it back in the box.
7. When replacing the fuse, replace it according to the amperage marked next to the fuse holder.
8. Without permission, do not open the control box and the voltage doubling cylinder, otherwise it will affect the product warranty. The manufacturer is not responsible for self-disassembly.
9. During transportation, the instrument should avoid rain erosion, and be strictly protected from collision and falling.