XZB-44kVA/22kV Variable Frequency Series Resonance Test Device
XZB-44kVA/22kV Variable Frequency Series Resonance Test Device
I. Test Object and Test Requirements
1. AC withstand voltage test for 10kV/300mm2 cable with length of 1km, capacitance ≤0.3755uF, test frequency 30-300Hz, test voltage 22kV, test time 5min.
II. Working Environment
1. Ambient temperature: -100C –500C;
2. Relative humidity: ≤90%RH;
3. Altitude: ≤1000m;
III. Main Technical Parameters and Functions of the Device
1. Rated capacity: 44kVA;
2. Input power: single-phase 220V or three-phase 380V voltage, frequency 50Hz;
3. Rated high voltage output: 22kV;
4. Output frequency range: 30-300Hz;
5. Frequency adjustment step: 0.1Hz;
6. Output voltage waveform: sine wave, waveform distortion rate ≤1%;
7. Voltage regulation sensitivity: 1%;
8. Measurement accuracy: voltage 1.0%, current 1.0%;
9. Timing range: 0-99min;
10. Protection function: overvoltage, overcurrent, zero-start, flashover, etc.;
11. Display: LCD display, Chinese menu operation;
12. Working power supply: AC 220V±10%, 50Hz;
13. Weight: about 15kg;
14. Dimensions: 400×300×200mm;
15. Applicable standards: DL/T 849.6-2004, GB/T 16927.1-1997, etc.
IV. System Composition and Configuration
1. Variable frequency power supply: 1 set;
2. Excitation transformer: 1 set;
3. High voltage reactor: 2 sets;
4. Capacitive voltage divider: 1 set;
5. Internal connection cables: 1 set.
V. Equipment List
1. Variable frequency power supply: 1 unit;
2. Excitation transformer: 1 unit;
3. High voltage reactor: 2 units;
4. Capacitive voltage divider: 1 unit;
5. Test leads: 1 set.
VI. Reference Standards
GB/T 16927.1-1997, DL/T 849.6-2004, DL/T 596-1996, GB 50150-2006, etc.
VII. After-sales Service
1. Free training on equipment operation and maintenance;
2. One-year warranty, lifetime maintenance;
3. 24-hour technical support hotline.