1. Voltage:DC 900V 1200V 1600V three ranges


2. Discharge current>100A/10US


3. Weight: 420g


4. Length: 450cm


5. Test interval time: 1 second


6. Number of tests: 300 times


7. Charging: 3~4 hours


 



Instructions


Edit


1. Please charge before use. To ensure charging effectiveness and extend battery life, use the dedicated charger. It takes about 3-4 hours to fully charge an empty battery. The red light on the charger indicates charging; the green light indicates charging is complete.


2. According to the installation height of the counter, appropriately extend the telescopic discharge rod.


3. For the dedicated grounding wire, insert one end plug into the rear socket of the calibrator, and connect the other end clip to the earth.


4. Press the red button to turn on high voltage for about 1 second. When the indicator light lights up (flickers slightly),


you can gently tap the connection point between the counter and the lightning arrester for testing.


5. After each tap, the discharge rod tip should be removed from the counter. If repeated testing is needed, do not release the button. Wait 1-2 seconds until the indicator light flickers again, then tap again for testing.


6. Continuous testing may cause the calibrator to heat up. Please allow appropriate intervals to reduce malfunctions and extend battery life.


7. The calibrator output has three levels: high, medium, and low, which can be adjusted via the toggle switch on the head to suit different types or brands of counters.


8. If the indicator light does not flash after pressing the button for more than 3 seconds, the battery needs charging.


9. Do not disassemble the calibrator arbitrarily. If the battery capacity drops significantly or charging efficiency is too low, it needs to be replaced.